| Application | Commercial | |
|---|---|---|
| General | Design | Direct acting spring control pressure regulator with in-built pressure reducing valve type balance regulating unit to ensure a constant outlet pressure. | 
| Connection Orientation | Inline Inlet & Outlet connection | |
| Installation | Suitable for indoor/Outdoor installations, tamper proof and corrosion resistance | |
| Installation Position | Horizontal/Vertical | |
| Flow | Capacity | Upto 250 m3/hr | 
| Pressure & Temperature | Design Pressure | 6 bar | 
| Inlet Pressure Range | 2.5 bar(g) – 6.0 bar(g) | |
| Nominal Outlet Pressure | 2 bar | |
| Creep Relief Valve | 2.4 ± 0.1 bar | |
| Over Pressure Shut-Off | 3.0 ± 0.1 bar | |
| Under Pressure Shut -Off | 1.5 ± 0.1 bar | |
| Connections | Inlet X Outlet | 1“ X 2”, 150# Flanged As per customer requirement | 
| Material | Casing | Pressure Die Casted Aluminium Alloy | 
| Internals | Elastomers | Nitrile Rubber (Buna-N) | 
| Internals | Aluminium, Derylin & Stainless Steel | |
| Others | Suitable For | Natural Gas & LPG | 
| Filter | Optional | |
| Failure Position | Closed | |
| Type of Reset | Manual |